Business Safety Checklist

 

Exterior Premises

  • Address-identifiable
  • Access-maintained
  • Hydrants-3' clearance around
  • Housekeeping-not an arsonist target

Egress

  • Recognizable-exit signs
  • Unobstructed-nothing in exit pathways obstructing required exit width
  • Unlocked-all exit doors shall be unlocked during business hours, always providing ways to get out
  • Illuminated-means of egress must be illuminated when building is occupied
  • Combustible storage-prohibited near exits, exit enclosures, or under stairways

Electrical

  • Circuit Breaker Panel Boxes-labeled breakers, proper access in front of (30" x 78")
  • Electrical/Mechanical Room Housekeeping-no combustible storage allowed
  • Overloaded circuits?  Recommend extra circuit or use power taps
  • Extension cords-plugged into outlet or power tap directly, not piggybacked, proper size, not used as substitute for permanent wiring, serves only one portable appliance, listed for intended use
  • Power Taps (Power Strips)-shall be listed, directly plugged into permanently installed receptacle, not piggybacked
  • Electric Motors-maintained & clean

Fire Extinguisher

  • Training-"PASS"
  • Proper extinguishers
    • Low hazard-min. 2A10BC, 75' travel dist.
    • Ordinary hazard-min. 2A10BC (30'), 2A20BC (50')
    • Extra hazard-min. 4A40BC (30'), 4A80BC (50')  
    • Type K in commercial kitchens-within 30' of heat producing equipment
  • Proper locations-near exit doors where possible, not exceeding maximum travel distance, properly mounted (max. 5' high if <40 lbs., max 3 ½' if >40 lbs.  In all cases, min. 4" above ground)
  • Proper maintenance-annual service required, six year service collar on extinguishers requiring a 12 year hydrostatic test

Fire/Smoke Separations

  • Properly maintained-self closing doors not propped open, smoke and fire doors able to fully close upon activation

Flammable Storage

  • Liquid storage indoors-> 10 gallons must be stored in liquid storage cabinet(s)
  • Retail Class 1 liquids-max. total 30 gal. unsprinklered building, 60 gal. sprinklered building; max. height 6' on metal shelves or 4' 6" on pallets, piles or racks; max. metal container size=5 gal.;   no combustibles stored above.  

Heat Sources

  • Ignition sources-prohibited near fumes, clearance to combustibles to be maintained
  • Portable Heaters-tip over and high temperature limiting features required and 3' clearance to combustibles

Combustible Materials/Storage

  • Combustible indoor storage-to be orderly, 2' from ceiling (unsprinklered), 18" or more below sprinkler heads
  • Combustible outdoor storage- dumpsters min. 5' from buildings, 10' from property lines
  • Decorations-to be non-flammable or treated flame resistant

Fire Protection/Detection Maintenance

  • Sprinkler system-annual service
  • Alarm system-annual service
  • Kitchen hood suppression system-6 mos. Service
  • Standpipe systems-every 5 years

Special Occupancy Requirements